Product

Copper Busway

Medium Voltage Busway

MV Cast Resin Insulated Busway(Copper Busway)

Description
As a leading manufacturer of Busway(Busbar Systems), our products have a reputation for quality.
TECOBAR Medium Voltage Cast-Resin Insulated Busway is developed for power systems between3.6kV~24kV.
Copper Busway of Medium Voltage Busway has features of safety and compact. It is designed to using
insulation material to perform cast resin sealing to the copper (aluminium) conductor. The insulation
material is cast resin containing non-organic volcanic rock and has excellent insulation characteristics
and mechanical strengh, humidity-proof, non-combustible, and self-extinguishing features.

Specification

Type PE Series
Model PE10 PE10 PE10 PE16 PE16 PE16
Conductor Section(mm2 ) 600 800 1200 1600 1920 2400
Conductor Dimensions (mm) w100xt6 w100xt8 w100xt12 w160xt10 w160xt12 w160xt15
             
Conductor Material purity copper 99.9% , above 98% IACS
Rated Current A (35/40 ℃) 1950 2174 2637 3203 3500 4019
Rated Voltage V 24kV
Frequency Hz 50/60
             
Electrical Characteristics
R at 20 ℃ μΩ∕m 28.9 21.7 14.4 10.8 9.3 7.4
R at 85 ℃ μΩ∕m 48.5 39.0 26.5 23.3 19.5 14.8
X μΩ∕m
f:60Hz
138.9 136.3 131.4 108.3 107.0 105.2
Icw kA / 1Sec 100 100 100 100 100 100
Ipeak 260 260 260 260 260 260
Ploss W∕m 553 553 553 717 717 717
IP/IK IP67/IK10
※Technical specifications may change without any further notice.
   
Product Dimensions (mm)
Width (B)∕Height(H) 550x150 550x210
B'xH' 650x360 650x360
Product Weight kg/m 100 105 110 145 148 153
※Please contact us for specific layouts and connection details.
※SH type has no protection cover required. However, SH type is advised to add aluminum cover for outdoor use.
For detail please contact us or local dealers.
※Please refer to the temperature correction coefficient of rated current on page 2-27 while ambient temperature exceeds 40℃.
 
Type PH Series 
Model PH10 PH10 PH10 PH10 PH16 PH16 PH16 PH20 PH20 PH20
Conductor Section(mm2 ) 600 800 1000 1200 1280 1600 1920 2000 2400 3000
Conductor Dimensions (mm) w100xt6 w100xt8 w100xt10 w100xt12 w160xt8 w160xt10 w160xt12 2-w100xt10 2-w100xt12 2-w100xt15
                     
Conductor Material purity copper 99.9% , above 98% IACS
Rated Current A (35/40 ℃) 2070 2308 2560 2800 3215 3525 3711 4208 4535 5000
Rated Voltage V 7.2kV 17.5kV
Frequency Hz 50/60
                     
Electrical Characteristics
R at 20 ℃ μΩ∕m 28.9 21.7 17.3 14.4 13.5 10.8 9.1 8.7 7.2 5.8
R at 85 ℃ μΩ∕m 39.9 32.1 26.1 21.8 21.4 17.8 16.1 14.4 12.4 10.2
X μΩ∕m
f:60Hz
157.8 154.9 152.1 149.4 123.8 122.9 121.7 85.7 84.9 83.8
Icw kA / 1Sec 100 100 100 100 80 80 80 100 100 100
Ipeak 260 260 260 260 208 208 208 260 260 260
Ploss W∕m 513 513 513 513 665 665 665 765 765 765
IP/IK IP67/IK10
※Technical specifications may change without any further notice
   
Product Dimensions (mm)
Width (B)∕Height(H) 322x150 322x210 322x260
BB 340 340 340
B'xH' 415x225 415x285 415x335
Product Weight kg/m 78 80 83 90 113 120 128 149 159 173
※Please contact us for specific layouts and connection details.
※SH type has no protection cover required. However, SH type is advised to add aluminum cover for outdoor use.
For detail please contact us or local dealers.
※Please refer to the temperature correction coefficient of rated current on page 2-27 while ambient temperature exceeds 40℃.
 
Type SH Series  
Model SH1 SH1 SH1 SH2 SH2 SH2
Conductor Section(mm2 ) 300 480 720 800 1000 1200
Conductor Dimensions (mm) w60xt5 w60xt8 w60xt12 w100xt8 w100xt10 w100xt12
             
Conductor Material purity copper 99.9% , above 98% IACS
Rated Current A (35/40 ℃) 1040 1295 1500 1710 1880 2018
Rated Voltage V 7.2kV
Frequency Hz 50/60
             
Electrical Characteristics
R at 20 ℃ μΩ∕m 57.7 36.1 24.1 21.7 17.3 14.4
R at 85 ℃ μΩ∕m 73.6 47.6 35.5 30.1 24.9 21.6
X μΩ∕m f:60Hz 128.7 126.5 124.3 89.9 88.3 87.0
Icw kA / 1Sec 50 50 50 80 80 80
Ipeak 130 130 130 208 208 208
Ploss W∕m 239 239 239 264 264 264
IP/IK IP67/IK10
※Technical specifications may change without any further notice.
   
Product Dimensions (mm)
Width (B)∕Height(H) 160x100 160x140
BB 200 200
B'xH' 250x155 250x195
Product Weight kg/m 48 51 56 74 77 81
※Please contact us for specific layouts and connection details.
※SH type has no protection cover required. However, SH type is advised to add aluminum cover for outdoor use.
For detail please contact us or local dealers.
※Please refer to the temperature correction coefficient of rated current on page 2-27 while ambient temperature exceeds 40℃.
 

  • Medium Voltage Busway
  • Low Voltage Busway
  • TECO