Product

Aluminum Busway

Medium Voltage Busway

MV Cast Resin Insulated Busway(Aluminum Busway)

Description
Our company specializes in manufacturing professional Busway(Busbar Systems) and Medium Voltage Busway. TECOBAR Medium Voltage Cast-Resin Insulated Busway is developed for power systems between3.6kV~24kV. Copper Busway of  Medium Voltage Busway has features of safety and compact. It is designed to using insulation material to perform cast resin sealing to the copper (aluminium) conductor. The insulation material is cast resin containing non-organic volcanic rock and has excellent insulation characteristics and mechanical strengh, humidity-proof, non-combustible,and self-extinguishing features.
Specification

Type PE Series
Model PE10 PE10 PE10 PE16 PE16
Conductor Section(mm2 ) 600 800 1200 1600 2400
Conductor Dimensions (mm) w100xt6 w100xt8 w100xt12 w160xt10 w160xt15
           
Conductor Material AL:1070
Rated Current A (35/40 ℃) 1438 1660 2004 2667 3210
Rated Voltage V 24kV
Frequency Hz 50/60
           
Electrical Characteristics
R at 20 ℃ μΩ∕m 47.2 35.4 23.6 17.7 11.8
R at 85 ℃ μΩ∕m 89.2 66.9 45.9 33.6 23.2
X μΩ∕m
f:60Hz
138.9 136.3 131.4 108.3 105.2
Icw kA / 1Sec 100 100 100 100 100
Ipeak 260 260 260 260 260
Ploss W∕m 553 553 553 717 717
IP/IK IP67/IK10
※Technical specifications may change without any further notice.
   
Product Dimensions (mm)
Width (B)∕Height(H) 550x150 550x210
B'xH' 650x360 650x360
Product Weight kg/m 89 91 94 115 122
※Please contact us for specific layouts and connection details.
※SH type has no protection cover required. However, SH type is advised to add aluminum cover for outdoor use.
For detail please contact us or local dealers.
※Please refer to the temperature correction coefficient of rated current on page 2-27 while ambient temperature exceeds 40℃.
 
Type PH Series 
Model PH10 PH10 PH10 PH10 PH16 PH16 PH16 PH20 PH20 PH20
Conductor Section(mm2 ) 600 800 1000 1200 1280 1600 1920 2000 2400 3000
Conductor Dimensions (mm) w100xt6 w100xt8 w100xt10 w100xt12 w160xt8 w160xt10 w160xt12 2-w100xt10 2-w100xt12 2-w100xt15
                     
Conductor Material AL:1070
Rated Current A (35/40 ℃) 1607 1815 2030 2223 25.2 2736 2897 3332 3580 4005
Rated Voltage V 17.5kV 17.5kV
Frequency Hz 50/60
                     
Electrical Characteristics
R at 20 ℃ μΩ∕m 47.2 35.4 28.3 23.6 22.1 17.7 14.7 14.2 11.8 9.4
R at 85 ℃ μΩ∕m 66.2 51.9 41.5 34.6 35.4 29.6 26.4 23.1 19.9 15.9
X μΩ∕m
f:60Hz
157.8 154.9 152.1 149.4 123.8 122.9 121.7 85.7 84.9 83.8
Icw kA / 1Sec 65 85 100 100 80 80 80 100 100 100
Ipeak 260 260 260 260 208 208 208 260 260 260
Ploss W∕m 513 513 513 513 665 665 665 765 765 765
IP/IK IP67/IK10
※Technical specifications may change without any further notice
   
Product Dimensions (mm)
Width (B)∕Height(H) 322x150 322x210 322x260
BB 340 340 340
B'xH' 415x225 415x285 415x335
Product Weight kg/m 67 69 71 74 105 110 116 143 152 164
※Please contact us for specific layouts and connection details.
※SH type has no protection cover required. However, SH type is advised to add aluminum cover for outdoor use.
For detail please contact us or local dealers.
※Please refer to the temperature correction coefficient of rated current on page 2-27 while ambient temperature exceeds 40℃.

  • Medium Voltage Busway
  • Low Voltage Busway