Aluminum Busway

LB Series

Aluminum

Description
TECOBAR Low Voltage Cast-Resin Insulated Busway is developed for electrical systems below 1kV.

The product has features of safety and compact. It is designed to use the insulation material to perform cast resin sealing to the copper (aluminium) conductor. The insulation material is cast resin which contains non-organic volcanic rock with the features of excellent insulation characteristics, mechanical strengh, humidity-proof, non-combustible, and self-extinguishing .
Features
Specification
Type Single Line Double Lines
Model LB12EA LB16EA LB08DA LB12DA LB16DA
Conductor Section(mm2 ) 1200 1600 1920 2400 3840
Conductor Dimensions (mm) 2-w120xt5 2-w160xt5 4-w80xt6 4-w120xt5 4-w160xt6
Conductor Material AL:1070
Rated Current A (35/40 ℃) 2094 2574 3395 4015 5375
Rated Voltage V 1000
Frequency Hz 50/60
Electrical Characteristics
R at 20 ℃ μΩ∕m 23.5 17.7 14.7 11.8 7.4
R at 90 ℃ μΩ∕m 30.8 22.9 19.7 15.9 11.5
X μΩ∕m
f:60Hz
27.2 21.2 25.5 21.0 16.1
Icw kA / 1Sec 100 100 120 120 120
Ipeak 220 220 264 264 264
Ploss W∕m 405 455 681 769 997
IP/IK IP68/IK10
※Technical specifications may change without any further notice
Product Dimensions (mm)
Width (B)∕Height (H)
3Φ3W+1/2G(Fig.1) 168/160 168/200 468/120 468/160 468/200
3Φ4W+1/2G(Fig.2 Fig.3)
Weight kg∕m
Product Weight 53.5 63.6 79.0 101.1 135.0
※ Conductor :
3Φ3W represents R S T three phases, three wires.
3Φ4W represents NRST three phases, four wires.
1/2G represents grounding phases 50% of rated current.
※ Please refer to the temperature correction coefficient of rated current on page 1-29 while ambient temperature exceeds 40℃.

Features
Applicable Scope:
TECOBAR busway is manufactured in accordance with IEC 60439-1, IEC 60439-2, IEC 61439 and CNS 14286. The elements included as below:
  1. Straight elements, elbow elements, geometrical shape elements, phase-switch elements, expansion elements, transfer elements, split elements and terminal elements.
  2. Distribution unit: There are fixed type take-off unit and draw-out type plug-in unit.
  3. * Note: The plug-in leads shall be reserved in advance. Therefore, the number of plug-in unit shall be confirmed while purchase.
Condition of Use:
TECOBAR busway is composed of the elements listed in item 3.1. The elements are connected through junction units on site before cast molding with insulation mix to complete the low voltage busway. Conditions for TECOBAR:
  1. Altitude: below 2000m, indoor and outdoor site.
  2. Ambient temperature: -45℃~65℃
  3. Ambient humidity: 0%~100%
Technical Specifications:
  1. Rated Voltage V : AC1000V.
  2. Rated Current A : 419A~8421A.
  3. Frequency Hz : 50/60.
  4. System : 3Φ3w, 3Φ4w, 3Φ3w+1/2G, 3Φ3W+G, 3Φ4W+1/2G, 3Φ4W+G.
  5. Conductor Material : Copper (E-Cu57) and Aluminum.
    Purity : 99.9% Conductivity : Above 98% IACS.
    According to standards : JIS H3140 , DIN 1787, DIN 1759, DIN 40500.
  6. Electrical characteristics of each TECOBAR element (less than 4m)
    Insulation capabilities :
    ◎ AC voltage withstand phase to phase is AC 5kV/1min.
    ◎ Insulation resistance phase to phase is ≧ 2GΩ/DC 1kV.

    Fireproof :
    ◎ In accordance with CNS 14286 at 840℃ for 30 minutes.
    ◎ In accordance with IEC 60331-21 at 750℃ for 3 hours.
    ◎ In accordance with BS 6387 950℃ for 3 hours.

    Protection degree :
    ◎ In accordance with IEC 60529 IP68.

    Mechanical impacts :
    ◎ In accordance with IEC 62262 IK10.

    Grounding :
    ◎ Internal grounding for TECOBAR busway system.

Product Design Theory
1. Temperature correction coefficient for rated current
Maximum ambient temperature ℃ 20 25 30 35 40 45 50 55 60
Daily average ambient temperature ℃ 15 20 25 30 35 40 45 50 55
Correction coefficient 1.18 1.14 1.09 1.05 1.00 0.94 0.88 0.82 0.75
2.Voltage drop calculation
  • △U =√3 x Is x L x (R cosθ+X sinθ) x 10-6
  • △U =Voltage drop (Volts)
  • Is =Load current (Amps)
  • L =Line length (m)
  • R =Resistance (μ Ω/m)
  • X =Reactance (μ Ω/m)
  • cosθ =Power factor
  • sinθ =√(1-cos 2θ)
3. Product model identification
LA 08 E C 5 - 480
LA Product series code LA:Low voltage 1kV LA series
LB:Low voltage 1kV LB series
NLV:Low voltage 1kV NLV series
08 Copper bar width 04 w=40mm , 08 w=80mm , 12 w=120mm , 16 w=160mm, 20 w=200mm,
24 w=240mm,
E Single/Double conductor of each phase E Single line D Double line
C Conductor type C Copper conductor A Aluminium conductor
5 No. of conductors
480 Cross sectional area of 2 conductor(mm 2 ) 480mm 2