TECOBAR Medium Voltage Cast-Resin Insulated Busway is developed for power systems between 1kV~24kV. The product has features of safety and compact. It is designed to using insulation material to perform cast resin sealing to the copper (aluminium) conductor. The insulation material is cast resin containing non-organic volcanic rock and has excellent insulation characteristics and mechanical strengh, humidity-proof, non-combustible, and self-extinguishing features.
Specification
Model | PH 10 | PH 16 | PH 20 | |||||||
Conductor Marteial | Aluminum | |||||||||
IP / IK | IP 68 / IK 10 | |||||||||
Frequency (Hz) | 50 / 60 Hz | |||||||||
Rated Voltage (V) | 7.2kV ~ 17.5kV | |||||||||
ln (A) norm | 1600 | - | 2000 | - | 2500 | - | - | 3150 | - | 4000 |
ln (A) 35/40°C | 1607 | 1815 | 2030 | 2223 | 2502 | 2736 | 2897 | 3332 | 3580 | 4005 |
Cond mm² | 600 | 800 | 1000 | 1200 | 1280 | 1600 | 1920 | 2000 | 2400 | 3000 |
R20 μΩ/m | 46.6 | 35.7 | 29.8 | 25.8 | 23.8 | 19.8 | 16.9 | 15.9 | 12.9 | 11.9 |
R85 μΩ/m | 58.5 | 44.8 | 37.4 | 32.4 | 29.9 | 24.9 | 21.2 | 19.9 | 16.2 | 14.9 |
X μΩ/m | 150 | 148 | 146 | 144 | 117 | 115 | 114 | 99 | 98 | 96 |
lcw kA/1Sec | 85 | 85 | 85 | 85 | 100 | 100 | 100 | 100 | 100 | 100 |
Ipeak kA | 216 | 216 | 216 | 216 | 255 | 255 | 255 | 255 | 255 | 255 |
Ploss 90 W/m | 456.7 | 442.7 | 455.4 | 477.6 | 569.3 | 553.4 | 524.1 | 661.3 | 604.4 | 728.7 |
Total Weight kg/m |
84 | 86 | 88 | 91 | 124 | 129 | 135 | 166 | 175 | 187 |
B x H mm | 322 x 150 | 322 x 210 | 322 x 260 | |||||||
B' x H' mm | 572 x 318 | 572 x 378 | 572 x 428 |
※Please contact us for specific layouts and connection details.
※SH type has no protection cover required. However, SH type is advised to add aluminum cover for outdoor use.
※For detail please contact us or local dealers.
※SH type has no protection cover required. However, SH type is advised to add aluminum cover for outdoor use.
※For detail please contact us or local dealers.

Features
Applicable Scope:
TECOBAR medium voltage busway is manufactured in accordance with, IEC 60694, IEC 62271-200, IEC 62271-201, IEC 62271-202 and IEEE C37.23 standards. The elements included as below: 3.1 Straight elements, Elbow elements, T-elements and Terminal elements, etc.
Condition of Use:
TECOBAR medium voltage busway is composed of the parts listed in item 3.1. The elements are connected through junction units on site before cast molding with insulation mix to complete the medium voltage busway. Conditions for TECOBAR:Frequency Hz: 50/60
System Type: 3Φ3w.
Conductor Material : Copper
Purity : 99.9% Conductivity : Above 98% IACS.
According to standards : JIS H3140 , DIN 1787, DIN 1759, DIN 40500.
Electrical characteristics of each TECOBAR element:
Partial discharge : ◎ Partial discharge coulomb value less than 20pC.
Protection degree : ◎ In accordance with IEC 60529 IP68.
Mechanical impacts : ◎ In accordance with IEC 60068-2 IK10. Insulation capabilities : ◎ Max 50kV/1min. (PE Type)
TECOBAR medium voltage busway is manufactured in accordance with, IEC 60694, IEC 62271-200, IEC 62271-201, IEC 62271-202 and IEEE C37.23 standards. The elements included as below: 3.1 Straight elements, Elbow elements, T-elements and Terminal elements, etc.
Condition of Use:
TECOBAR medium voltage busway is composed of the parts listed in item 3.1. The elements are connected through junction units on site before cast molding with insulation mix to complete the medium voltage busway. Conditions for TECOBAR:
- Altitude: below 1000m, indoor or outdoor site.
- Ambient temperature: -20℃~65℃
- Ambient humidity: 0%~100%
Purity : 99.9% Conductivity : Above 98% IACS.
According to standards : JIS H3140 , DIN 1787, DIN 1759, DIN 40500.
Partial discharge : ◎ Partial discharge coulomb value less than 20pC.
Protection degree : ◎ In accordance with IEC 60529 IP68.
Mechanical impacts : ◎ In accordance with IEC 60068-2 IK10. Insulation capabilities : ◎ Max 50kV/1min. (PE Type)
Product Design Theory
1. Temperature correction coefficient for rated current
Maximum ambient temperature ℃ | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 |
Daily average ambient temperature ℃ | 15 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 |
Correction coefficient | 1.18 | 1.14 | 1.09 | 1.05 | 1.00 | 0.94 | 0.88 | 0.82 | 0.75 |
2.Voltage drop calculation
- △U =√3 x Is x L x (R cosθ+X sinθ) x 10-6
- △U =Voltage drop (Volts)
- Is =Load current (Amps)
- L =Line length (m)
- R =Resistance (μ Ω/m)
- X =Reactance (μ Ω/m)
- cosθ =Power factor
- sinθ =√(1-cos 2θ)
PH | 10 | E | C | 3 | - | 1000 |
PH | Product series code | SH: 7.2kV PH: 17.5kV PE: 24kV | ||||
10 | Copper bar width | 10 w=100mm , 16 w=160mm , 20 w=200mm | ||||
E | Single/Double conductor of each phase | E Single line D Double line | ||||
C | Conductor type | C Copper conductor A Aluminium conductor | ||||
3 | No. of conductors | |||||
1000 | Cross sectional area of conductor(mm 2 ) | 1000mm 2 |
4.For calculation of general product data or technical information, please contact with manufacturer or local agency.